Thirteen power system questions on per-unit, faults, stability, protection and inverters, what each one tests, and answers that survive the follow-up.
These questions cover five areas that power system roles commonly draw on: per-unit and three-phase basics, power flow, fault current, stability, and protection. Prepare a sixth as well: what changes when inverter-based solar, wind and batteries replace spinning generators. Interviewers rarely stop at the definition; the follow-up checks whether you have used the idea on a real one-line diagram. Each question below gives what it tests, a short answer and the likely follow-up. If the role is power electronics or power supply design, skip to the last section: that is a different interview.
Check which job the interview is for
"Power systems" covers several jobs, and the same question gets a different best answer in each.
- Role — What to prepare most — What a strong answer shows
- Transmission planning — Power flow, contingency analysis, stability — You can set up a study, read the results and say what you would change
- Protection and control — Fault current, relays, coordination, grounding — You know why a relay should or should not trip for a given fault
- Distribution and DER interconnection — Voltage drop, power factor correction, inverter-based resources — You can explain a hosting or voltage problem to a customer or a planner
- Power electronics or power supply design — Converters, switching devices, magnetics — You can size a converter on paper and explain the trade-offs
If you want an outside check on which topics the profession treats as core, the NCEES specification for the PE Electrical and Computer: Power exam (effective October 2025) is a good one. Of its 80 questions, 10 to 15 each go to protection, circuit analysis (which includes symmetrical components and the per-unit system) and electrical safety, and 8 to 12 to transmission and distribution analysis, which covers power flow, fault current and stability. Siemens PSS/E is one study tool you may meet; it handles power flow, contingency, dynamic and short-circuit studies.
Expect a licensing question too. The US Bureau of Labor Statistics notes that entry-level jobs do not require a license, and that a PE license usually takes a degree, the FE exam, several years of experience and the PE exam. Say plainly where you are on that path.
Fundamentals
1. Why do we use the per-unit system?
What it tests: whether you have done fault or power flow calculations by hand.
Answer: Per-unit expresses every quantity as a fraction of a base value. You pick two bases, usually power and voltage, and derive the rest, so base impedance is V² / S. The main gain is that an ideal transformer disappears from the model, because per-unit values are the same on both sides when the voltage bases follow the turns ratio. Similar equipment has similar per-unit impedance whatever its size, so a wrong value stands out.
Follow-up: "Convert this transformer's impedance to a 100 MVA base." Use Z_new = Z_old × (V_old / V_new)² × (S_new / S_old).
2. What are active, reactive and apparent power, and why does reactive power matter?
What it tests: whether you connect reactive power to voltage, not just to power factor.
Answer: Active power (W) does the work. Reactive power (var) sustains the magnetic and electric fields of the load and does no net work. Apparent power (VA) is their vector sum, and power factor is active over apparent. Reactive power matters because it supports voltage: a system short of it sees voltage sag, and correcting power factor near the load cuts current, losses and voltage drop.
Follow-up: "Capacitor bank or synchronous condenser?" A capacitor's output falls with the square of voltage, so it gives least when the system needs most. A synchronous condenser's reactive output rises as voltage falls, and its spinning mass adds inertia, which is why they have come back as generators retire.
3. Why do we transmit power at high voltage?
What it tests: basic losses reasoning.
Answer: For the same power, higher voltage means lower current, and resistive loss goes with the square of current. The US Energy Information Administration puts transmission and distribution losses at about 5% of the electricity moved in 2018 to 2022.
Power flow
4. What is a load flow study, and what are the bus types?
What it tests: whether you know what a study solves for.
Answer: A power flow study finds the voltage magnitude and angle at each bus in steady state, then the real and reactive flow on every line and the losses. A load (PQ) bus has real and reactive power specified, so its voltage magnitude and angle are unknown. A generator (PV) bus has real power and voltage magnitude specified. One slack bus has its voltage and angle fixed and picks up whatever the losses turn out to be.
Follow-up: "Which solution method, and why?" Newton-Raphson is the usual choice. Gauss-Seidel uses little memory but converges more slowly. Fast-decoupled load flow separates the real and reactive problems for speed, and DC power flow is a linear, real-power-only approximation that always converges but is less accurate.
Faults and short-circuit current
5. What types of faults occur, and which is most common?
What it tests: fault analysis vocabulary, and symmetrical components.
Answer: Balanced (three-phase) faults and unbalanced ones: single line-to-ground, line-to-line and double line-to-ground. Commonly cited figures put single line-to-ground at roughly 65 to 70% of transmission line faults, with three-phase faults at about 5%. Unbalanced faults are solved with symmetrical components, the method Fortescue published in 1918: you split the unbalanced quantities into positive, negative and zero sequence networks and connect them according to the fault type.
6. How do you calculate short-circuit current?
What it tests: whether you can do it on a whiteboard. This is the question to practise until it is automatic.
Worked example: a 10 MVA transformer with 8% impedance feeds a 13.8 kV bus. Assume the utility source behind it is infinite.
- Fault MVA at the bus is 10 / 0.08 = 125 MVA.
- Fault current is 125,000,000 / (√3 × 13,800), about 5,230 A.
- Say what the assumption does: an infinite source makes this the highest current the transformer allows. Adding the real source impedance in series lowers it.
Then say what the number is for: checking breaker interrupting ratings and setting relays.
Stability and frequency
7. What kinds of power system stability are there?
What it tests: whether you can name the problem before solving it.
Answer: Rotor angle stability is whether generators stay in synchronism, after a small disturbance (small-signal) or a large one such as a fault (transient). Voltage stability is whether bus voltages hold up, and it is closely tied to reactive power. Frequency stability is whether the system recovers frequency after losing generation or load. An IEEE Power and Energy Society report in 2020 extended the classification with resonance and converter-driven stability, because power electronics now cause problems the older classes did not cover.
Follow-up: "How do you improve transient stability?" Start with clearing faults faster: the shorter the fault, the less time the generator rotors have to speed up and pull out of step.
8. A large generator trips. What happens to frequency?
What it tests: the order of events.
Answer: Frequency starts to fall, and the stored energy in spinning machines (inertia) sets how fast. Turbine governors then raise output, and automatic generation control adjusts the governors to bring frequency back to its scheduled value. Inverter-based resources are not electromechanically coupled to the grid, so a system with fewer synchronous machines sees a faster rate of change of frequency unless something else responds quickly.
Protection
9. Compare overcurrent, distance and differential protection.
What it tests: whether you can pick a scheme for a piece of equipment.
Answer: Overcurrent is the simplest and suits radial distribution, where high current means a fault downstream. Distance relays respond to the ratio of voltage to current, which tracks how far away the fault is, so they suit transmission lines. Differential protection compares current entering and leaving a zone such as a transformer, generator or bus, and only responds to faults inside it. Zones overlap so nothing is left unprotected, and delayed backup covers a relay that fails.
Follow-up: "Why might a distance relay trip with no fault?" Heavy load also lowers the measured impedance, so it can look like a fault.
10. Vacuum or SF6 circuit breaker: which goes where?
What it tests: a common trap, which is treating the two as interchangeable.
Answer: Vacuum interrupters are the core of medium-voltage breakers and have largely replaced SF6 there. The EPA says the largest use of SF6 is in high-voltage circuit breakers. Then add the context: EPA rates SF6 as 23,500 times more effective than carbon dioxide at trapping heat, with an atmospheric life above 1,000 years, and vacuum breakers have reached 145 kV.
11. Solidly grounded or resistance grounded?
What it tests: that you see grounding as a trade-off.
Answer: A solidly grounded system gives high ground fault current, so faults are easy to detect and clear quickly. A low-resistance grounded system limits ground fault current to a moderate level (the source gives 25 A or greater as the dividing line from high-resistance grounding) and relies on a ground fault relay to trip the breaker. A high-resistance grounded system limits it to 25 A or less and can keep running with one ground fault, which suits plants where an unplanned shutdown is costly, but the first fault must be found before a second one forces a trip.
Inverter-based resources
12. What changes when inverters replace synchronous generators?
What it tests: whether your knowledge is current.
Answer: A grid-following inverter synchronises to the existing grid voltage and injects current, so it adds no inertia and does not strengthen a weak grid. Grid-forming inverters set their own voltage, closer to how a synchronous machine behaves. Name the standards: IEEE 2800-2022 covers inverter-based resources on transmission, including ride-through and reactive power control, and IEEE 1547-2018 covers distributed resources on distribution systems.
If the role is power electronics or power supply design
13. Size the power stage of a buck converter.
What it tests: whether you can get from a spec to component values.
Worked example: 12 V in, 3.3 V out, estimated 90% efficiency. Following Texas Instruments' application note, duty cycle is D = Vout / (Vin × η) = 3.3 / (12 × 0.9), about 31%. Ripple current is ΔI = (Vin − Vout) × D / (fs × L). Without a recommended inductor, choose ripple at 20 to 40% of maximum output current and solve for L. The peak switch current is the output current plus half the ripple, and the inductor rating must exceed it.
Follow-up: "What happens if you raise the switching frequency?" From the ripple formula, the same ripple needs a smaller inductor.
A one-week preparation plan
- Days 1 and 2: redo per-unit conversion and the fault calculation in question 6 by hand, then add a source impedance and redo it.
- Day 3: set up a three-bus power flow on paper and label every bus type.
- Day 4: explain the frequency response after a generator trip, and grid-following versus grid-forming, out loud.
- Day 5: pick one transformer and one line and say which protection you would use and why.
- Day 6: prepare two project stories in STAR form, one where you caught an error in a study or design. Our STAR interview questions guide shows the structure.
- Day 7: map each requirement in the job ad to a question above.
For broader coverage, see our electrical engineering interview questions and, for electronics roles, the electronics and communication interview questions.
If you want help in the interview itself, Verve AI's Interview Copilot listens to the conversation and shows suggestions only you can see, drawing on the resume and job details you upload. Check the pricing page for what each plan includes.
Sources
- PE Power exam format and question counts by topic (effective October 2025): https://ncees.org/wp-content/uploads/2025/04/PE-Electrical_Power_Oct_2025.pdf
- PE Power exam is computer based, 80 questions, 9-hour appointment: https://ncees.org/exams/pe-exam/electrical-and-computer/
- Licensing path and entry-level licensing: https://www.bls.gov/ooh/architecture-and-engineering/electrical-and-electronics-engineers.htm
- PSS/E study types: https://www.siemens.com/global/en/products/energy/grid-software/planning/pss-software/pss-e.html
- Per-unit system, base values and change of base: https://en.wikipedia.org/wiki/Per-unit_system
- Synchronous condenser reactive output and renewed use for inertia: https://en.wikipedia.org/wiki/Synchronous_condenser
- Transmission and distribution losses, about 5% in 2018 to 2022: https://www.eia.gov/tools/faqs/faq.php?id=105&t=3
- Power flow bus types and solution methods: https://en.wikipedia.org/wiki/Power-flow_study
- Fault types and commonly cited frequencies: https://en.wikipedia.org/wiki/Electrical_fault
- Symmetrical components, Fortescue 1918: https://en.wikipedia.org/wiki/Symmetrical_components
- IEEE PES 2020 report extending stability definitions (resonance, converter-driven): https://resourcecenter.ieee-pes.org/publications/technical-reports/pes_tp_tr77_psdp_stability_051320
- Frequency control, rate of change of frequency and inverter-based resources: https://en.wikipedia.org/wiki/Utility_frequency
- Overcurrent, distance and differential protection, overlapping zones and backup: https://en.wikipedia.org/wiki/Power_system_protection
- Differential protection responds only to faults inside its zone: https://en.wikipedia.org/wiki/Protective_relay
- Distance relay V/I principle and tripping under heavy load: https://en.wikipedia.org/wiki/Distance_relay
- Vacuum interrupters in medium-voltage breakers, 145 kV unit: https://en.wikipedia.org/wiki/Vacuum_circuit_breaker
- SF6 in high-voltage breakers, warming potential and lifetime: https://www.epa.gov/eps-partnership/sulfur-hexafluoride-sf6-basics
- Solid, low-resistance and high-resistance grounding: https://en.wikipedia.org/wiki/Ground_%28electricity%29
- Grid-following and grid-forming inverters: https://en.wikipedia.org/wiki/Grid-forming_inverter
- IEEE 2800-2022 scope: https://standards.ieee.org/ieee/2800/10453/
- IEEE 1547-2018 scope: https://standards.ieee.org/ieee/1547/5915/
- Buck converter duty cycle, ripple and inductor selection: https://www.ti.com/lit/an/slva477b/slva477b.pdf
- Interview Copilot shows suggestions visible only to the user: https://docs.vervecopilot.com/features/interview-copilot
- Personalisation from resume and job details: https://docs.vervecopilot.com/features/create-first-persona